The Victron Energy MultiPlus-II 48/10000/140-100 is a battery charger with dimensions of 677 x 363 x 206 mm and a weight of 48.8 kg.
Last updated: 11 November 2026
Battery and charging
- Charger output voltage
- 57.6V
- Charger output current
- 140A
- Shore or generator current it passes
- 100 A transfer switch
- Highest charge current it will take
- 140 A maximum
“Charge voltage 'absorption' 57.6V”
Source: victronenergy.com/media/pg/MultiPlus-II_230V/en/technical-specifications-mp-ii-230v.html
“Charge current house battery (4) 110A 140A”
Source: victronenergy.com/media/pg/MultiPlus-II_230V/en/technical-specifications-mp-ii-230v.html
“Transfer switch 32 A 50 A 100 A 100 A 100 A”
Source: victronenergy.com/upload/documents/Datasheet-MultiPlus-II-inverter-charger-EN-.pdf
“Max. battery charge current (4) 120 /70 / 35 A 220/120/ 70 A 110 A 140 A 200 A”
Source: victronenergy.com/upload/documents/Datasheet-MultiPlus-II-inverter-charger-EN-.pdf
Battery care and safety
- Ingress protection
- IP 22
“Protection category IP 22”
Source: victronenergy.com/media/pg/MultiPlus-II_230V/en/technical-specifications-mp-ii-230v.html
Size and fit
- Weight
- 48.8 kg
- Overall dimensions
- 677 x 363 x 206 mm
“Weight 41.2 kg 48.8 kg 80 kg Dimensions h x w x d 642 x 363 x 206 mm 677 x 363 x 206 mm”
Source: victronenergy.com/media/pg/MultiPlus-II_230V/en/technical-specifications-mp-ii-230v.html
“Dimensions h x w x d 642 x 363 x 206 mm 677 x 363 x 206 mm”
Source: victronenergy.com/media/pg/MultiPlus-II_230V/en/technical-specifications-mp-ii-230v.html
Compatibility
- Battery voltage it runs on
- 38-66 V at the input
“DC Input voltage range 12 V - 9,5-17 V 24 V - 19-33 V 48 V - 38-66 V”
Source: victronenergy.com/upload/documents/Datasheet-MultiPlus-II-inverter-charger-EN-.pdf
Other findings
- Absorption voltage
- 57,6 V absorption
- CE mark date
- CE mark from May 2019
- Declared EU directives
- EMC, Low Voltage, RoHS and REACH
- Named on declaration of conformity
- Named on the February 2026 EU declaration
“Charge voltage 'absorption' 14,4 / 28,8 / 57,6 V”
Source: victronenergy.com/upload/documents/Datasheet-MultiPlus-II-inverter-charger-EN-.pdf
“CE MARK DATE: May, 2019”
Source: victronenergy.com/upload/documents/DoC-MultiPlus-II-(EU)-0226.pdf
Unconfirmed
“EMC Directive 2014/30/EU Low Voltage Directive 2014/35/EU RoHS (2011/65/EU and 2015/863/EU) EC REACH Regulation (EC 1907/2006)”
Source: victronenergy.com/upload/documents/DoC-MultiPlus-II-(EU)-0226.pdf
“MultiPlus-II 48/10000/140-100 230V”
Source: victronenergy.com/upload/documents/DoC-MultiPlus-II-(EU)-0226.pdf
Charger certifications
IECEE CB Test Certificate NL2-020381 M1, issued by Kiwa Nederland B.V. (Apeldoorn) on 2023-11-28 and signed by Raphael Rader, for a "Battery inverter/charger" found in conformity with IEC 60335-1:2010 with AMD1:2013 and AMD2:2016, and IEC 60335-2-29:2016 with AMD1:2019, under test report 17PP264-33_1. It replaces NL2-020381 of 2022-10-10 "due to update of CBTR to include new models to the family". It names six MultiPlus-II 230V models (with their GX and MultiGrid-II twins): 24/3000/70-32, 48/3000/35-32, 48/5000/70-50, 48/8000/110-100, 48/10000/140-100 and 48/15000/200-100. THIS CERTIFICATE'S RATINGS FOR THIS MODEL ARE MISPRINTED: under the 48/8000, 48/10000 and 48/15000 it repeats the 24/3000's, 48/3000's and 48/5000's figures word for word (the 48/8000 appears as "24Vdc nom, 19-33Vdc 125A max"). Kiwa's IEC 62109 certificate DE/PTZ/0356/M1 prints this model's real ratings. The model is named in the certificate's Model / Type Ref. list, so the certificate covers it; its ratings block is not used as a figure for anything.
IECEE CB Test Certificate DE/PTZ/0356/M1, issued by Kiwa Primara GmbH (Kaufbeuren) on 2023-10-25 and signed by Tanja Rottach, for a "Battery inverter/charger" found in conformity with IEC 62109-1:2010 and IEC 62109-2:2011, under test reports 17PP264-31_1 and 17PP264-32_1. It replaces DE/PTZ/0356 of 2022-09-08 and adds the 48/8000/110-100, 48/10000/140-100 and 48/15000/200-100. It names the same six MultiPlus-II 230V models as the IEC 60335 certificate. IEC 62109 is the safety standard for power converters in photovoltaic systems, which is why a battery inverter/charger that can run grid-parallel carries it.
- IEC 60335-1Household and similar electrical appliances — Safety — Part 1: General requirementsStated in manufacturer documentIssuer: Kiwa Nederland B.V. (IECEE CB Scheme National Certification Body)Cert #NL2-020381 M1Kiwa Nederland B.V. certificate NL2-020381 M1 — Victron MultiPlus-II — victronenergy.com/upload/documents/Certificate-IEC-60335-1-60335-2-MultiPlus-II-(GX)-3kVA,-5kVA,-8kVA,-10kVA-&-15kVA.pdfView standard: Household and similar electrical appliances — Safety — Part 1: General requirements →
Applies in: IECEE CB Scheme member countries
- IEC 60335-2-29Household and similar electrical appliances — Safety — Part 2-29: Particular requirements for battery chargersStated in manufacturer documentIssuer: Kiwa Nederland B.V. (IECEE CB Scheme National Certification Body)Cert #NL2-020381 M1Kiwa Nederland B.V. certificate NL2-020381 M1 — Victron MultiPlus-II — victronenergy.com/upload/documents/Certificate-IEC-60335-1-60335-2-MultiPlus-II-(GX)-3kVA,-5kVA,-8kVA,-10kVA-&-15kVA.pdfView standard: Household and similar electrical appliances — Safety — Part 2-29: Particular requirements for battery chargers →
Applies in: IECEE CB Scheme member countries
- IEC 62109-1Safety of power converters for use in photovoltaic power systems — Part 1: General requirementsStated in manufacturer documentIssuer: Kiwa Primara GmbH (IECEE CB Scheme National Certification Body)Cert #DE/PTZ/0356/M1Kiwa Primara GmbH certificate DE/PTZ/0356/M1 — Victron MultiPlus-II — victronenergy.com/upload/documents/Certificate-EN-IEC-62109-1-2-all-MultiPlus-II-(GX).pdfView standard: Safety of power converters for use in photovoltaic power systems — Part 1: General requirements →
Applies in: IECEE CB Scheme member countries
- IEC 62109-2Safety of power converters for use in photovoltaic power systems — Part 2: Particular requirements for invertersStated in manufacturer documentIssuer: Kiwa Primara GmbH (IECEE CB Scheme National Certification Body)Cert #DE/PTZ/0356/M1Kiwa Primara GmbH certificate DE/PTZ/0356/M1 — Victron MultiPlus-II — victronenergy.com/upload/documents/Certificate-EN-IEC-62109-1-2-all-MultiPlus-II-(GX).pdfView standard: Safety of power converters for use in photovoltaic power systems — Part 2: Particular requirements for inverters →
Applies in: IECEE CB Scheme member countries
Each standard listed is an independent claim about this specific product — one standard does not imply compliance with another.
Sources
- Kiwa Nederland B.V. certificate NL2-020381 M1 — Victron MultiPlus-IICertification body record
Kiwa Nederland B.V.
Source: victronenergy.com/upload/documents/Certificate-IEC-60335-1-60335-2-MultiPlus-II-(GX)-3kVA,-5kVA,-8kVA,-10kVA-&-15kVA.pdf
Retrieved September 23, 2026
- Kiwa Primara GmbH certificate DE/PTZ/0356/M1 — Victron MultiPlus-IICertification body record
Kiwa Primara GmbH
Source: victronenergy.com/upload/documents/Certificate-EN-IEC-62109-1-2-all-MultiPlus-II-(GX).pdf
Retrieved September 23, 2026
- Archived document
Source: victronenergy.com/upload/documents/Datasheet-MultiPlus-II-inverter-charger-EN-.pdf
Retrieved September 16, 2026
- Archived document
Source: victronenergy.com/upload/documents/DoC-MultiPlus-II-(EU)-0226.pdf
Retrieved September 23, 2026
- 7. Technical specificationsArchived document
Source: victronenergy.com/media/pg/MultiPlus-II_230V/en/technical-specifications-mp-ii-230v.html
Retrieved November 11, 2026