Pytes V5°
The Pytes V5° is a battery pack with a nominal voltage of 51.2V, a continuous discharge of 100 A, 6000 cycles, a weight of 44kg/97lbs (44kg) and CAN/RS485 communication.
Last updated: 28 October 2026
Battery and charging
- Voltage
- 51.2V
- Rated charge cycles
- 6000 cycles
- Battery type
- LFP
- Maximum continuous discharge
- 100A
- Peak discharge
- 101A~120A(3min) ; 121A~180A(15sec)
- Recommended charging
- 75A
- Series and parallel limit
- 16 pcs (81.92kWh) in a group 6 groups (491.52kWh) in a system w/a Hub
- Highest charge current it will take
- 100A
- Efficiency
- 95%
- Working voltage range
- 47.5V~57.6V
Row from the maker’s page: “Nominal Voltage” | “51.2V”
Source: pytesess.com/Low-Voltage-Battery/v5.html
Row from the maker’s page: “Cycle Life” | “6000 cycles”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
“Chemistry LFP Communication Protocol CAN/RS485 Dimensions(L x W”
Source: pytesess.com/Low-Voltage-Battery/v5.html
Row from the maker’s page: “Max Continuous Charge/Discharge Current” | “100A”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
Row from the maker’s page: “Peak Charge/Discharge Current” | “101A~120A(3min) ; 121A~180A(15sec)”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
Row from the maker’s page: “Recommended Charge/Discharge Current” | “75A”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
“Scalability 16 pcs (81.92kWh) in a group 6 groups (491.52kWh) in a system w/a Hub”
Source: pytesess.com/Low-Voltage-Battery/v5.html
Row from the maker’s page: “Max Continuous Charge/Discharge Current” | “100A”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
Row from the maker’s page: “Round-Trip Efficiency” | “95%”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
Row from the maker’s page: “Voltage Range” | “47.5V~57.6V”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
Battery care and safety
- Operating temperature range
- -10°C~50°C/14°F~122°F
- Heating built into the battery
- Temperature Rise: 18°F/h
“Ambient Temperature -10°C~50°C/14°F~122°F”
Source: pytesess.com/Low-Voltage-Battery/v5.html
Row from the maker’s page: “Heating Pad” | “Temperature Rise: 18°F/h”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
Size and fit
- Weight
- 44kg
- Overall dimensions
- Sources disagree
442*530*140mm/17.40*20.87*5.51inch(3.2U)
“Dimensions(L x W x H) 442*530*140mm/17.40*20.87*5.51inch(3.2U)”
Source: pytesess.com/Low-Voltage-Battery/v5.html
17.32*20.87*5.51 inch (3.2U)
Row from the maker’s page: “Dimensions (L*W*H)” | “17.32*20.87*5.51 inch (3.2U)”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
- Terminals
- PHOENIX M6 Bolt
- Stated weight
- 44kg/97lbs
- Series and parallel connection
- Sources disagree
16 pcs (81.92kWh) in a group 6 groups (491.52kWh) in a system w/a Hub
“Scalability 16 pcs (81.92kWh) in a group 6 groups (491.52kWh) in a system w/a Hub”
Source: pytesess.com/Low-Voltage-Battery/v5.html
14 pcs (71.68kWh) in a group 6 groups (430.08kWh) in a system w/a Hub
Row from the maker’s page: “Scalability” | “14 pcs (71.68kWh) in a group 6 groups (430.08kWh) in a system w/a Hub”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
Row from the maker’s page: “Weight” | “44kg/97lbs”
Source: pytesess.com/Low-Voltage-Battery/v5.html
“Connection Options V5°: PHOENIX M6 Bolt V5°α: Amphenol SurLok Plus 8.0mm”
Source: pytesess.com/Low-Voltage-Battery/v5.html
Row from the maker’s page: “Weight” | “44kg/97lbs”
Source: pytesess.com/Low-Voltage-Battery/v5.html
Compatibility
- Communication protocol
- CAN/RS485
Row from the maker’s page: “Communication Protocol” | “CAN/RS485”
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
“Communication Protocol CAN/RS485”
Source: pytesess.com/Low-Voltage-Battery/v5.html
Certification claims
- Standard certified to
- UL9540 Ed.2 (2020), UL9540A, UL1973, CEC, SGIP, CE, IEC62619, UN38.3
“UL9540 Ed.2 (2020), UL9540A, UL1973, CEC, SGIP, CE, IEC62619, UN38.3”
Source: pytesess.com/Low-Voltage-Battery/v5.html
Sources
- Residential Solar Battery-Lfp Battery-Manufacturer-Company-SupplierArchived document
Source: pytesess.com/Low-Voltage-Battery/v5.html
Retrieved October 28, 2026
- Archived document
Source: pytesusa.com/public/upload/20230807/5b6a8a53cfc7a2f2eb06ebc3885efd77.pdf
Retrieved October 28, 2026