Skip to content

Midac MFT

Last updated: 3 November 2026

Battery and charging

Boost voltage it applies
14.1 (2.35Vpc) - 14.4 (2.40Vpc)

Row from the maker’s page: “Boost voltage (20 °C / 68 °F) 12V bloc” | “14.1 (2.35Vpc) - 14.4 (2.40Vpc)”

Source: midacbatteries.com/wp-content/uploads/2026/02/SPE-MFT_STANDBY_EN-11_2023-5014011-1005-00.pdf

Float voltage
13.44 (2.24Vpc) - 13.68 (2.28Vpc)

Row from the maker’s page: “Float voltage (20 °C / 68 °F) 12V bloc” | “13.44 (2.24Vpc) - 13.68 (2.28Vpc)”

Source: midacbatteries.com/wp-content/uploads/2026/02/SPE-MFT_STANDBY_EN-11_2023-5014011-1005-00.pdf

How fast it loses charge sitting idle
less than 3%/month at 20 °C

“Self-discharge: less than 3%/month at 20 °C (68 °F)”

Source: midacbatteries.com/wp-content/uploads/2026/02/SPE-MFT_STANDBY_EN-11_2023-5014011-1005-00.pdf

Battery care and safety

Operating temperature range
-20 to +60 °C

Row from the maker’s page: “Operation” | “-20 to +60 °C”

Source: midacbatteries.com/wp-content/uploads/2026/02/SPE-MFT_STANDBY_EN-11_2023-5014011-1005-00.pdf

Size and fit

Terminals
FT

“Designed as standard with adaptor terminal type FT”

Source: midacbatteries.com/wp-content/uploads/2026/02/SPE-MFT_STANDBY_EN-11_2023-5014011-1005-00.pdf

Sources

  • Archived document

    Source: midacbatteries.com/wp-content/uploads/2026/02/SPE-MFT_STANDBY_EN-11_2023-5014011-1005-00.pdf

    Retrieved November 2, 2026