Epoch Batteries SR48100H 51.2V 100Ah LiFePO4 Battery Pack

SKU SR48100H

Epoch Batteries
Epoch Batteries' product page

Last updated: 23 September 2026

Battery and charging

Usable energy (kilowatt-hours)
4.92 kWh usable of 5.12 nominal

“Nominal voltage 51.2 V 2.2 Nominal […] 5.12 KWh Usable […] 4.92KWh 2.3 Nominal […] 100Ah”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_SR48100H_battery_specification_V02.pdf?v=1700284600

Maximum charge voltage
56.0 V charge

“C harge voltage 56.0V 2.6 Float voltage 54.6V 2.7 Al lowed MAX charge current 7 0A”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_SR48100H_battery_specification_V02.pdf?v=1700284600

Internal resistance
30 milliohms or less

“Internal resistance @1khz AC ≤ 3 0 m O hm”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_SR48100H_battery_specification_V02.pdf?v=1700284600

Recommended charging
50A*N (N is the Quantity of the battery pack)

“7 Rated charging current limited value 50A*N (N is the Quantity of the battery pack)”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Maximum charge current, as the maker labels it
70 A permitted

“C harge voltage 56.0V 2.6 Float voltage 54.6V 2.7 Al lowed MAX charge current 7 0A”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_SR48100H_battery_specification_V02.pdf?v=1700284600

Charging voltage
56.0V

“1 Absorption voltage 56.0V 2 Float voltage 54.6V”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Float voltage
54.6 V float

“C harge voltage 56.0V 2.6 Float voltage 54.6V 2.7 Al lowed MAX charge current 7 0A”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_SR48100H_battery_specification_V02.pdf?v=1700284600

Voltage it cuts off at
48.0V; restart at 52V; generator start at ≥50V

“6 Low Voltage cut-off 48.0V”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Other findings

Heater current is not seen by the BMS
The heater's draw is invisible to the BMS

“2. The current of the heating film is calculated in addition and is not added to the current detected by the BMS. 3. If the battery system is fully charged for the first time, the heating is stopped after a delay of 1 hour.”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Heating activation condition
Heats between -25 and 5 °C, if charging above 0.08C

“Max parallel number 32pcs Operation temperature 1 Charge: -10~50 ℃ Discharge:-20~50 ℃ Heating opening condition2 -25 ℃ ≤ T ≤ 5 ℃ @ I≥0.08C Heating completion condition3 T ≥ 12 ℃ Storage temperature @off mode 0 ℃ <T<30 ℃ < 6 months -10 ℃ <T<45 ℃ < 3 months Recommended environment 15~35 ℃ , 5~75%RH”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Inverter configuration
Force charge Enable

“11 Force charge Enable For more information to connect with different inverter/charger”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Low state of charge cutoff
4%

“5 Low SOC cut-off 4% 6 Low Voltage cut-off 48.0V”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Maximum discharge current
100 A permitted

“Allowed MAX discharge current 100A 2.10 Recommend d ischa r ge current ≤ 50A 2.1 1 Peak/Surge current limit <119A@5mins < 200 A@ 15 s”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_SR48100H_battery_specification_V02.pdf?v=1700284600

Maximum parallel units
Up to 32 in parallel

“Max parallel number 32pcs Operation temperature 1 Charge: -10~50 ℃ Discharge:-20~50 ℃ Heating opening condition2 -25 ℃ ≤ T ≤ 5 ℃ @ I≥0.08C Heating completion condition3 T ≥ 12 ℃ Storage temperature @off mode 0 ℃ <T<30 ℃ < 6 months -10 ℃ <T<45 ℃ < 3 months Recommended environment 15~35 ℃ , 5~75%RH”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Over discharge recovery window
Recharge within 24 hours of over-discharge

“nerator or other energy source within 24h if the battery is over discharged, otherwise, it may be damaged.”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672

Peak surge current
119 A for 5 min, 200 A for 15 s

“Allowed MAX discharge current 100A 2.10 Recommend d ischa r ge current ≤ 50A 2.1 1 Peak/Surge current limit <119A@5mins < 200 A@ 15 s”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_SR48100H_battery_specification_V02.pdf?v=1700284600

Recommended discharge current
50 A recommended

“Allowed MAX discharge current 100A 2.10 Recommend d ischa r ge current ≤ 50A 2.1 1 Peak/Surge current limit <119A@5mins < 200 A@ 15 s”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_SR48100H_battery_specification_V02.pdf?v=1700284600

Storage duration by temperature
6 months at 0-30 °C, 3 months at -10-45 °C

“Max parallel number 32pcs Operation temperature 1 Charge: -10~50 ℃ Discharge:-20~50 ℃ Heating opening condition2 -25 ℃ ≤ T ≤ 5 ℃ @ I≥0.08C Heating completion condition3 T ≥ 12 ℃ Storage temperature @off mode 0 ℃ <T<30 ℃ < 6 months -10 ℃ <T<45 ℃ < 3 months Recommended environment 15~35 ℃ , 5~75%RH”

Source: cdn.shopify.com/s/files/1/0251/0484/2798/files/Epoch_Rack_User_manual_-_R1.pdf?v=1700283672