Battery and charging
- Recommended continuous discharge
- 50
- Recommended charging
- 10
- Series and parallel limit
- 6 units
- Highest charge current it will take
- 50
- Maximum discharge current, as the maker labels it
- 100
- Voltage at which a charger restarts
- 49.0
“Recommended discharge current limit = 50 A”
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1
“Recommended Charge Current = 10 A”
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1
“A total of 6 units can be connected in parallel, for total installed capacity of 31.2kWh @C2, 25°C.”
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1
“Maximum Continuous Charge Current limit = 50 A”
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1
“Maximum discharge Current limit = 100 A”
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1
“V reconnect 3.06 V 49.0V Mains or generator must reconnect to charge batteries.”
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1
Battery care and safety
- Pack storage advice
- store batteries in a cool and well-ventilated area – ideally 25°C ± 3°C
“Always store batteries in a cool and well-ventilated area – ideally 25°C ± 3°C.”
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1
Size and fit
- How it mounts
- 19” (11U) server racks
“The BlueNova® 52V RacPower range has been designed to be installed in 19” (11U) server racks.”
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1
Sources
- BN-UserManual 52V-5 2k BP RacPowerArchived document
Source: bluenova.zohodesk.com/portal/en/kb/articles/bn-usermanual-52v-5-2k-bp-racpower-202000508-rev1