Skip to content

Discover Battery 48-48-5120-H

The Discover Battery 48-48-5120-H is a battery pack with a nominal voltage of 51.2 and 5120 Wh of energy.

Last updated: 16 October 2026

What battery it needs

Circuit breaker it requires
Dual 100 A (2 Pole Ganged)

“Breaker Dual 100 A (2 Pole Ganged) Dual 100 A (2 Pole Ganged)”

Source: discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf

Battery and charging

Energy (kilowatt-hours)
5.12 kWh

“Nominal Energy 5.12 kWh 5.12 kWh”

Source: discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf

Maximum charge voltage
Charge Absorption Voltage - U1 MAX 55.2

“Charge Bulk Voltage - Bulk Vdc 55.2 Charge Absorption Voltage - U1 MAX 55.2 Charge Float Voltage - U2 53.6 Charge Termination Current(a) 2.5 A Low Voltage Disconnect Recommended 48 Low Voltage Disconnect (b) 43.2”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

Energy
5120 Wh

“900-0067 51.2 100 5120 48-48-5120-H”

Source: discoverbattery.com/s4x_files/resources/discover-lithium-sds.pdf

Voltage
51.2

“900-0067 51.2 100 5120 48-48-5120-H”

Source: discoverbattery.com/s4x_files/resources/discover-lithium-sds.pdf

Rated capacity
Rated Capacity kWh (1 HR) 5.12

“Nominal Energy (kWh) 5.12 Useable DoD 100% Rated Capacity kWh (1 HR) 5.12 Rated Capacity Ah (1 HR) 100”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

Rated charge cycles
10x the life of lead-acid battery (BCI-06)

“10x the life of lead-acid battery (BCI-06)”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

Maximum efficiency
Up to 98%

“• Up to 98% round-trip efficiency”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

Peak discharge
Peak Discharge Current (3 seconds) 218 A RMS

“Max. Discharge Current (1 hour) 95 A Max. Continuous Discharge Current 70 A Max. Charge Current (1 hour) 95 A Max. Continuous Charge Current 70 A Peak Discharge Current (3 seconds) 218 A RMS”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

Highest charge current it will take
95 A

“Max Current (1 Hour) 95 A 95 A”

Source: discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf

Battery care and safety

Operating temperature range
Internal Heater Operating Temperature Range -17°C to 8°C (1.4°F to 46.4°F)

“Internal Heater Operating Temperature Range -17°C to 8°C (1.4°F to 46.4°F)”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

What the battery management system protects against
Linear scaling of charge, discharge and peak capacity

“Up to 184 kWh (per LYNK II Gateway) Linear scaling of charge, discharge and peak capacity”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

Size and fit

Overall dimensions
Industry Reference 19 inch - 3U rackmount

“Industry Reference 19 inch - 3U rackmount Length (A) (in/mm) 19.6 497.3 Width (B) (in/mm) / incl. Handles 17.3 / 19 439.2 / 482.6 Height (C) (in/mm) 5.3 133.5 Total Height (D) (in/mm) 5.3 133.5”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

Terminals
Amphenol SurLok Plus

“Terminal Amphenol SurLok Plus”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

“Terminals Amphenol SurLok Plus Amphenol SurLok Plus”

Source: discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf

Group the maker sells it as
19 Inch Rack Mount 3U

“Form Factor 19 Inch Rack Mount 3U 19 Inch Rack Mount 3U”

Source: discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf

Identity

Model designation
48-48-5120-H

“AES RACKMOUNT IS FOR RESIDENTIAL OFF-GRID SOLAR AND WHOLE HOME BACKUP POWER. Battery Module 48-48-5120 48-48-5120-H Form Factor 19 Inch Rack Mount 3U 19 Inch Rack Mount 3U L x W x H inch 19.6 x 17.3 x 5.3 19.6 x 17.3 x 5.3 L x W x H mm 497 x 439 x 133.5 497 x 439 x 133.5 Wei”

Source: discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf

Other name the manufacturer uses
900-0067

“900-0067 51.2 100 5120 48-48-5120-H”

Source: discoverbattery.com/s4x_files/resources/discover-lithium-sds.pdf

Buying and owning it

What it is said to be best for
RESIDENTIAL OFF-GRID SOLAR AND WHOLE HOME BACKUP POWER

“AES RACKMOUNT IS FOR RESIDENTIAL OFF-GRID SOLAR AND WHOLE HOME BACKUP POWER.”

Source: discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf

Certification claims

Certification claimed by the manufacturer
Certification Standards UL1973, UL9540, UL9540a, IEC 62619, CE

“Certification Standards UL1973, UL9540, UL9540a, IEC 62619, CE Shipping Classification UN 38.3, UN3480, Class 9 (Lithium batteries)”

Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

Sources

  • Archived document

    Source: discoverbattery.com/s4x_files/resources/discover-lithium-sds.pdf

    Retrieved October 13, 2026

  • Archived document

    Source: dev.discoverenergysys.com/s4x_files/resources/808-0040-aes-rackmount-48-48-5120-h-data-sheet.pdf

    Retrieved October 13, 2026

  • Archived document

    Source: discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf

    Retrieved October 13, 2026